滑动鼠标了解更多

Western Sahara TCMK5216 Automatic Fire Alarm Output Module

Payment Type: L/C,T/T,D/P,D/A,Paypal,Money Gram,Western Union
Incoterm: FOB,CFR,CIF,EXW,FAS,FCA,CPT,CIP
Transportation: Ocean
Port: Dalian

Product Description

Model No.
Place Of Origin

:TCMK5216
:China

 

Selling Units

:Others

 

Product Description

1. Base of the detector is shown below. There are 2 conductor pieces with terminals on the base. Detector' 5 loop should be respectively connected with
two terminals (non-polarized) After the base is fixed firmly, rotate the bottom of detector and base clockwise, and then the detector will be fitted to the base.
2.1.0 mm² or above fire cable, subject to local codes.


Voltage:Loop:DC24V (16V~28V); Power: DC24V (20V~28V)
Standby Current:Loop: ≤0.2mA;Power: ≤2mA
Action Current:Loop: ≤1.5mA;Power: ≤15mA
Operating Environment:Temperature: -10°C~+55°C; Relative Humidity: ≤95%, non-condensing
Output Capacity:6W/Module
Dimension (L×W×H):86mm×86mm×40mm (with base)
Approval:CCCF

Appearance: The control panel adopts Akzo anti-corrosion coating. No pun-gent smell, anti-static electricity, non-toxic harm, non-pollution, no waste. The cabinet is made of stainless steel, which is not easy to deform and high-end and elegance

The Control Panel Is Equipped With A Fire Alarm And A Fault Output Port. The Output Of 24V In Case Of Fire Al Arm And Fault Effectively Provides A Convenient Way For External Device

Power Box: Equipped With Main Power Supply Detec-Tion Function. Easily Achieved Switching Between The Main And Standby Power. Insurance Of Its Own Can Provide Protection To The Control Panel When The External Current Is Too High

Standby Battery: 12V/12Ah Battery *2, Work For 12 Hours Without Main Power, Work For 3 Hours Without Main Power And Alarm In The Loop. And The Battery Has Its Own Charging Function. Con-Trol Panel Is Exquisite And Beautiful.